About Us

products
products

RA-912F Portable SF6 Gas Comprehensive Analyzer

For determining the quality of SF6 gas.SF6 purity analyzer .SF6 Dew point analyzer and SF6 Decomposition product analyzer 3 in 1.


RA-912F allows the determination of up to three quality parameters with only one measurement:


SF6 concentration (%)


Moisture concentration


SO2 concentration (ppm)


1.Using the principle of SF6 gas spectral absorption measurements,


rapid, without the interference of other gas components to better meet the needs of the site.


2.SF6 purity mass ratio (g / g), volume ratio (mol/mol) switch at any time to display


can be directly controlled national standard, eliminating the volume and mass ratio conversion link.


3.Massive experimental data, based on real-time traffic temperature compensation.


4.Unique patented drying protection device.


5.Boot-up zero, the slope of the self-calibration.


6.Built-in gas filtration system


7.Each measuring gas path individually designed to ensure accuracy, independent regulation is more suitable for field use.


8.TFT touchscreen


9.Built-in printer


TECHNICAL DATA
Dimensions L 406 mm, W 538 mm, H 269 mm
Weight 15 kg
Input pressure 0.2 - 35 bar
Operating temperature -20 °C to +50 °C
Ambient moisture 15% up to 90 % relative moisture, non condensing during operation
Operating voltage 100-240 VAC, 50/60Hz
Number of measured values to be stored max.500
Interface USB

Drag left and right table


PURITY MOISTURE SO2 H2S CO
Measuring principle Thermal conductivity Electronic moisture measurement (capacitive) Electrochemical reaction Electrochemical reaction Electrochemical reaction
Measuring range 0 - 100 vol.% -80 to +20 °C 0 to 100 ppm
0 to 10 ppm0 to 2000ppm
0 to 100 ppm 0 to 500 ppm
Measuring accuracy ±2 %(F.S) ±2 ℃ ±5 % μL/L ±5 % μL/L ±5 % μL/L
Flow rate 250 to 350 mL/min
Recommend 300 mL/min
300 to 900 mL/min
Recommend 500 mL/min
100 to 120 mL/min
Recommend 100 mL/min
100 to 120 mL/min
Recommend 100 mL/min
100 to 120 mL/min
Recommend 100 mL/min
Reaction time < 30 s < 3 min < 60 s < 60 s < 60 s
Recommended calibration interval every one years every one years every one years every one years every one years